Table 4-1. Unit Preventive Maintenance Checks and Services for Model F10000RD
NOTE
If the equipment must be kept in continuous
operation, do only the procedures that can be done
without disturbing operation. Make complete checks
and services when the equipment is shut down.
The hourly intervals listed represent actual engine
operation as indicated on the hourmeter.
Location
Item
Item to
Not Fully Mission
No.
Interval
Check/
Procedure
Capable if:
Service
Refrigeration
Unit Interior
NOTE
The refrigeration unit must be shut down
with the battery disconnected, the left side
condenser door, and left front bottom door
must be open for the following 8 hour
PMCS.
1
8 Hours
Air Cleaner
Service the air cleaner by removing and cleaning
Air cleaner is missing or
it using compressed air.
clogged.
a.
Shut down refrigeration unit (para 2-7) and
disconnect battery (para 4-35).
b.
Open left side condenser door and left front
bottom door.
c.
Loosen clamp and remove air cleaner.
4-13