TM 9-4120-367-14 TM  07592B-14/1 4.17 LOW SUCTION PRESSURE. a. c. e. Other  indications: 1. Unit stops on low pressure cutout. 2. Frosted evaporator coil. Outside  air  temperature  below  0°F  (-18°C)  jumper  LPCO. Is pressure normal? Unit is operational. Check evaporator airflow (paragraph 4.3). 1.  Check  air  filter. 2.  Check  mist  eliminator. Repair or replace. Unit is operational. Solenoid valve L2 not closing. Repair or replace. b. Low  refrigerant  charge. Leak test, repair, and add refrigerant. Is  pressure  normal? Unit  is  operational. d. 4-49/(4-50 blank)