TM 9-4120-367-14
TM 07592B-14/1
5.6 RECTIFIER CR1. This task covers removal, testing and installation.
INITIAL SETUP
Applicable Configurations:
All
Test Equipmment:
Multimeter
Special Tools:
None
Materials/Parts:
None
Equipment Descriptions:
Power OFF; installed in shelter
Special Environmental Conditions:
None
General Safety Instructions:
See WARNING page
References:
None
Troubleshooting References:
None
Personnel Required:
Refrigeration Specialist
Location/Item
Removal
Action
a.
b.
c.
d.
e.
f.
Disconnect power supply.
Remove top cover from evaporator section.
Remove screws and pull junction box from frame.
Use care to avoid breaking sensing line.
Tag and pull the four quick disconnect" terminals
from the rectifier.
Remove capactors C1 and C2 or C6.
Remove two screws and pull rectifier from frame.
Remarks
High voltage can kill.
Sensing line connects TEM-
PERATURE SELECTOR to
sensing line bulb which is be-
hind return air louver.
5-12
|