5.8 RELAYS K4 (AND K5 ON MODEL MHP-20-4-08). - Continued
Testing
Action
d.
a.
b.
c.
Remove 28 Vdc power. Multimeter should indicate
that terminals 1 and 4, 5 and 6, and 10 and 7 are
dosed and that terminals 1 and 3, 5 and 11, and
10 and 8 are open.
Side heat-shrink tubing over the leads.
Group the leads and pull them through bracket.
Solder Ieads to relay. See figures FO-1, FO-3,
FO-5, FO-7, or FO-9.
K4 - Single-Phase Model F18H
X4B16V,
1
X12A16V
V9A20
2
X11A16V
3
X6A20V
4
X5B16V,
5
X10A16V
6
X8A20V
7
X9A16V
8
V1SA20N
9
X7A16V
10
11
K4 - 3-Phase Models F18H-3 & F18H-4
X7B16A
1
V9A20
2
X12A16A
3
X10A20A
4
X6B16B
5
X9A20B
6
7
X11A16C
8
V14A20N,
9
X44A12N
X5B16C
10
X13A16B
11
Remarks
NOTE
Terminals 5, 6, and 11 are not
used for Model F18H.
5-19
Location/Item
- Continued
Installation
Wire No.
Terminal No.
Blank
Blank
Wire No.
Terminal No.
X8A20C
|