5.24 CONDENSATE LINES. This task covers flow test, cleaning, removal and installation.
INITIAL SETUP
Applicable Configurations:
All
Test Equipment:
None
Special Tools:
None
Materials/Parts:
One Pint Container
Fresh Water
Brush or Soft Wire
Equipment Descriptions:
Power OFF; installed in shelter
Special Environmental Conditions:
None
General Safety Instructions:
See WARNING page
References:
None
Troubleshooting References:
None
Personnel Required:
Unit Maintenance
Location/Item
Flow Test
Action
a.
b.
c.
d.
e.
f.
g.
h.
i.
Remove mist eliminator.
Remove air filter.
Loosen mount bolts.
Place a 3/4-inch board under one side of the air
conditioner to tilt it slightly.
Pour about one pint (one-half liter) of water into the
lower end of the drip pan below the evaporator
coil.
Verify that the water flow out of the drip pan
through the drain tube.
Tilt the air conditioner the opposite direction, and
repeat the flow test on the other side.
Water should drain freely through both tubes. If it
does not, remove and repair or replace the drain
tube.
Tighten mounting bolts.
Remarks
Paragraph 5.21
Paragraph 5.20