TM 9-4120-367-14
TM 07592B-14/1
6.5 NITROGEN PURGE. - Continued
Location/Item
Action
Remarks
Purge
- Continued
Nitrogen pressure in the system
should not exceed 10 pounds.
e. Open cylinder valve and allow dry nitrogen to
flow through system until all moisture is forced
out (not less than 5 minutes).
f. Close cylinder valve.
g. Close both charging valves.
h. Disconnect all hoses.
Figure 6-3. Nitrogen Tank Connection
6-17
|