TM  9-4120-367-14 TM 07592B-14/1 6.6    EVACUATION.  -  Continued Location/Item Action Remarks Vacuum  Pump i. Open both charging valves. -  Continued j. Run the vacuum pump until at least 29 inches of mercury, measured on the vacuum pump gauge, is  reached. NOTE Inability to reach 29 inches of mercu- ry may indicate a leak or problem with the pump. k.  Continue running the pump for one more hour, observing the vacuum pump gauge. If the gauge needle moves back and forth, there is a refriger- ant leak which must be located and corrected. l.   Close manifold valves. m.  Close both charging valves. n.   Stop vacuum pump. Figure  6-4.  Evacuating  System 6-19