TM 9-4120-367-14
TM 07592B-14/1
3.5 INSTALLATION OR REMOVAL - Continued
Table 3-3. Connector Pin Wiring, Model F18H
Pin
Internal Wiring Connection J1 and J11
A
Positive
B
Neutral
C
Blank not used
D
Ground
E
Blank not used
Table 3-4. Phase Rotation Models F18H-3 and F18H-4
Pin
Internal Wiring Connection J1 and J11
A
Phase A
B
Phase B
C
Phase C
D
Ground
E
Blank not used
Location/Item
Installation
Action
a. Refer to table 3-1 for electric power supply re-
quirements.
b. Determine which input power connector is to be
used.
Do not wire connection J1 and J11 for use
at the same time, nor apply power source
to connectors J1 and J11 at the same time.
You could have unknown HOT connector,
radio interference, or you could place two
separate power supplies in opposition to
each other.
c. Remove all three top covers.
Remarks
There are three models, each
with a different requirement.
Rewire unit at terminal boards
TB3 and TB4, if necessary.
See tables 3-2, 3-3, and 3-4.
3 -8
|