ARMY TM 9-4120-381-14
NAVY EE-000-CA-MMA-010/7053-AC
AIR FORCE TO 35E9-136-31
4-89. CONDENSER FAN CONNECTING LINK ASSEMBLY.
This task covers:
a.
Inspection
b.
Adjust
c.
Removal
d.
Installation
INITIAL SETUP:
Tools
Tool kit, service, refrigeration unit (Item 1, Appendix B)
Personnel: 1
Equipment Conditions:
WARNING
Disconnect input power to the air conditioner before performing any internal maintenance. Voltages used
can KILL. Shutting the unit off at the control panel does not disconnect unit power.
1.
Disconnect air conditioner input power at source.
2.
Remove left front condenser panel (para 4-27).
INSPECTION
1.
Check that control rod (7) is not bent or damaged. Replace if damaged (see Figure 4-89).
2.
Check that connector swivels (5) and (9) are not damaged. Replace if damaged.
3.
Check for damaged, loose, or missing mounting hardware.
ADJUST
1.
Loosen screw (8) on actuator connector swivel (9) and close damper.
2.
Match mark control rod (7) next to connector swivel (9).
3.
Open damper with 1/2 inch (1.3 cm) clearance and match mark control rod (7).
4.
Measure damper rod marks for one inch (2.54 cm) between steps 2 and 3.
5.
If measurement between steps 2 and 3 is less than one inch (2.54 cm), repeat steps 1 thru 4.
6.
To test linkage operation contact Direct Support Maintenance.
REMOVAL
1.
Loosen screw (8) on actuator connector swivel (9).
2.
Loosen screw (6) on control lever connector swivel (5).
3.
Remove control rod (7).
4.
Remove locknut (10) and actuator connector swivel (9).
5.
Remove locknut (1) and control lever connector swivel (5).
6.
Remove bolt (3), locknut (4), and control lever (2).
4-174
|