Page Title: 3. BLOWN VALVE PLATE OR CYLINDER HEAD GASKETS.
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books
   

 

ARMY TM 9-4120-381-14 NAVY EE-000-CA-MMA-010/7053-AC AIR FORCE TO 35E9-136-31 Table 5-1.  Direct Support Troubleshooting - Continued MALFUNCTION TEST OR INSPECTION CORRECTIVE ACTION 3.  BLOWN VALVE PLATE OR CYLINDER HEAD GASKETS. Step 1.  Cylinder head bolts not properly torqued. a. Replace cylinder head gasket (para 5-47). b. Retorque cylinder head bolts to 30-35 lb-ft. Step 2.  Liquid refrigerant floodback or flooded start.  See malfunction 7. 4.  COMPRESSOR CYCLES ON LOW-PRESSURE CONTROL. Step 1.  Low refrigerant pressure switch erratic in operation. a. Check tubing to switch to see if clogged or crimped (para 5-24). b. Check switch setting (para 5-24). Step 2.  Insufficient refrigerant in system. Add refrigerant (para 5-17). Step 3.  Suction service valve closed. Backseat (counterclockwise) suction service valve (para 5-34). Step 4.  Restricted air flow through condenser. Clean condenser (para 4-90). Step 5.  Discharge service valve not fully open. Backseat (counterclockwise) discharge service valve (para 5-33). Step 6.  Air in system. Purge refrigerant system (para 5-13). 5.  COMPRESSOR CONTINUALLY CYCLES. Step 1.  Faulty high refrigerant pressure switch. Adjust or replace switch (para 5-23). Step 2.  Faulty low refrigerant pressure switch. Adjust or replace switch (para 5-24). Step 3.  Faulty low oil pressure switch. Adjust or replace switch (para 5-25). Step 4.  Condenser capacity reduced by refrigerant overcharge accompanied by high discharge pressure. Remove overcharge (para 5-17). Step 5.  Plugged drier filter. Replace drier filter (para 5-26). 5-3

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business