ARMY TM 9-4120-381-14 NAVY EE-000-CA-MMA-010/7053-AC AIR FORCE TO 35E9-136-31 Table 5-1.  Direct Support Troubleshooting - Continued MALFUNCTION TEST OR INSPECTION CORRECTIVE ACTION 6.  LOW DISCHARGE PRESSURE. Step 1.  Suction service valve partially closed. Backseat (counterclockwise) suction service valve (para 5-34). Step 2.  Leaky compressor suction valves. Remove cylinder head, examine valves and valve seats (para 5-47), replace if necessary. Step 3.  Worn piston rings. a. Check connecting rods pistons, and rings (para 5-49), replace if necessary. b. Check rods, pistons, and cylinder tolerances (para 5-49). c. If any cylinder bore is out of tolerance (para 5-49), replace compressor (para 5-46). 7.  FLOODING. Step 1.  Improperly set primary expansion valve. Adjust primary expansion valve (para 5-38). Step 2.  Improperly set liquid quench expansion valve. Adjust liquid quench expansion valve (para 5-36). Step 3.  Improperly set hot gas bypass valve Adjust hot gas bypass valve (para 5-37). Step 4.  Evaporator circulator fan failure. a. Check fan belt tension (para 4-69). b. Check evaporator motor (para 4-70). c. Check evaporator motor fan pulleys (para 4-72 and 4-73). d. Check evaporator circulator fan (para 4-71). 8.  LOW SUCTION PRESSURE. Step 1.  Insufficient refrigerant in system. Add refrigerant (para 5-17). Step 2.  Evaporator circulator fan failure. a. Check fan belt tension (para 4-69). b. Check evaporator motor (para 4-70). c. Check evaporator motor and fan pulleys (para 4-72 and 4-73). d. Check evaporator circulator fan (para 4-71). 5-4

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business