5-53. CONDENSER COIL.
This task covers:
Inspection
Repair
INITIAL SETUP:
Tools:
Tool kit, service, refrigeration unit (Item 1, Appendix B)
Material:
Rags (Item 12, Appendix E)
Personnel: 1
Equipment Conditions:
WARNING
Disconnect input power to the air conditioner before performing any internal maintenance. Voltages
used can KILL Shutting the unit off at the control panel does not disconnect unit power.
1. Disconnect air conditioner input power at source.
2. Remove left front condenser panel (para 4-27).
3. Remove right front condenser panel (para 4-28).
INSPECTION
1.
If a leak is suspected or indicated, test per paragraph 5-15.
2.
If coil is damaged beyond repair, contact General Support Maintenance.
REPAIR
1.
Repair of the condenser coil is limited to checking for leaks and brazing damaged tubing (paras 5-15 and 5-14).
2.
If condenser coil is beyond repair, contact General Support Maintenance.
FOLLOW ON PROCEDURE
1.
Install left front condenser panel (para 4-27).
2.
Install right front condenser panel (para 4-28).
3.
Check refrigerant charge (para 5-17).
4.
Connect air conditioner input power at source.
5-125
|