ARMY TM 9-4120-381-14
NAVY EE-000-CA-MMA-010/7053-AC
AIR FORCE TO 35E9-136-31
INSTALLATION
NOTE
If expansion valve body is not being installed, proceed to step 2.
If expansion valve body is being installed, proceed to disassembly before brazing valve body.
1.
Install expansion valve body (5) by brazing tubing (4) and distributor (3) at joints (para 5-14).
2.
Install sensing bulb (9) in retaining clamp (11).
3.
Tighten two screws (10) and nuts (12) on sensing bulb retaining clamp (11).
4.
Install two clamps (15) to refrigerant lines.
5.
Install two flat washers (14) and (16), one screw (17), and locknut (13).
6.
Install valve cap (8).
7.
Install external equalizer line (18).
8.
Leak test all brazed connections in repaired area (para 5-15).
FOLLOW ON PROCEDURE
1.
Install rear evaporator panel (para 6-6).
2.
Perform start up after repairs (para 5-22).
6-27
|