TM 9-4120-389-14
5-19. DAMPER ACTUATOR
Preliminary procedures:
1.
Remove top cover (See para. 4-14).
2.
Remove condenser outlet guard (See para. 4-21).
a.
Removal
WARNING
All refrigerant must be discharged from system before attempting to remove
damper actuator.
(1)
Discharge the system per para. 5-3.
(2)
Loosen set screw on actuator arm.
(3)
Remove actuator arm.
(4)
Loosen flare nut on actuator.
(5)
Remove two nuts and lockwashers that secure the damper actuator to thebracket.
(6)
Remove damper actuator.
Figure 5-16. Damper Actuator Removal/Replacement
5-48
|