TM 9-4120-389-14 5-19.  DAMPER ACTUATOR Preliminary procedures: 1. Remove top cover (See para.  4-14). 2. Remove condenser outlet guard  (See para.  4-21). a. Removal WARNING All   refrigerant   must   be   discharged   from   system   before   attempting   to   remove damper actuator. (1) Discharge the system per para.  5-3. (2) Loosen set screw on actuator arm. (3) Remove actuator arm. (4) Loosen flare nut on actuator. (5) Remove two nuts and lockwashers that secure the damper actuator to thebracket. (6) Remove damper actuator. Figure 5-16.  Damper Actuator Removal/Replacement 5-48