TM9 4120-423-14&P
TROUBLESHOOTING PROCEDURES FOR AIR CONDITIONER, SPLIT PACK
UNIT TROUBLESHOOTING
THIS WORK PACKAGE COVERS: Unit Troubleshooting
Tools and Special Tools
Personnel Required
Unit level technician
Equipment Conditions
Air conditioner installed in shelter
WARNING
Disconnect input power before performing internal electrical troubleshooting. Voltages
used can be lethal. Shutting the unit off at the control module does not disconnect power
to the various components of the air conditioner.
MALFUNCTION
1.
AIR CONDITIONER WILL NOT START IN ANY MODE
TEST OR INSPECTION
Step 1.
Press run indicator light.
CORRECTIVE ACTION
If light illuminates, go to step 6.
TEST OR INSPECTION
Step 2.
Check to see if air conditioner power circuit breaker in shelter has been turned off
or tripped
CORRECTIVE ACTION
Reset circuit breaker
0010 00-1
|