1.
AIR CONDITIONER WILL NOT START IN ANY MODE - Continued
TEST OR INSPECTION
Step 8.
Check power input to condenser.
CORRECTIVE ACTION
(a)
Remove power.
(b)
Remove electrical module from condenser section (see WP0051).
(c)
Apply power.
(d)
Test for 208 Vac between P12 pins:
D and E
D and F
E and F
(e)
If 197 to 229 Vac is present in all three phases, go to step 9.
(f)
If not, use electrical schematic or wiring diagram (WP0145), to locate defect.
(g)
Repair or replace defects as indicated.
TEST OR INSPECTION
Step 9.
Check DC voltage output.
CORRECTIVE ACTION
(a)
Make sure all connections have been restored.
(b)
Apply power.
(c)
Check for voltage between pins A and H of remote cable at washboard or P14.