TM9 4120-423-14&P
1.
AIR CONDITIONER WILL NOT START IN ANY MODE - Continued
(d)
If 25 to 31 Vdc is not indicated, go to steps 10 and 11.
TEST OR INSPECTION
Step 10.
Check electrical fuse F1 (See WP0036).
CORRECTIVE ACTION
(a)
Remove power.
(b)
Remove top cover, evaporator (See WP0026).
(c)
Remove fuse from fuseholder (on left side of electrical module assembly).
(d)
Examine fuse and test for continuity. Replace if bad.
TEST OR INSPECTION
Step 11.
Check transformer T1 output.
CORRECTIVE ACTION
(a)
Apply power.