Click here to make tpub.com your Home Page

Page Title: COOLING ACTION STOPS AFTER OPERATING A SHORT TIME
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM9 4120-423-14&P
TEST OR INSPECTION
Step 1. Check that fabric condenser cover is rolled up and tied.
CORRECTIVE ACTION
(a)
Roll up cover and tie securely (see WP0044).
(b)
Allow 30 minutes after compressor stops for pressure to drop to reset pressure.
(c)
Manually reset high-pressure switch (S4).
TEST OR INSPECTION
Step 2. Check outside covers on condenser section.
CORRECTIVE ACTION
(a)
Remove power.
(b)
Inspect condenser section for loose, damaged, or missing covers and screws.
(1)
Tighten loose screws.
(2)
Install missing covers and screws.
(3)
Repair or change damaged covers.
(4)
Allow 30 minutes after compressor stops for pressure to drop to reset
pressure.
(5)
Manually reset high-pressure switch (S4).
(6)
Apply power.
TEST OR INSPECTION
Step 3. Check for blocked condenser EMI screens.
CORRECTIVE ACTION
Remove blockage/clean EMI screens.
TEST OR INSPECTION
Step 4. Check relay K2. (See WP0051).
CORRECTIVE ACTION
Replace if found bad.
0010 00-7