MALFUNCTION
3.
EVAPORATOR BLOWER MOTOR FAILS TO START. (Compressor, condenser blower
motor, and heaters start).
TEST OR INSPECTION
Step 1. Check relay K3. (See WP0038)
CORRECTIVE ACTION
Replace if found bad.
TEST OR INSPECTION
Step 2. Check motor B3. (See WP0030)
CORRECTIVE ACTION
Replace if found bad.
MALFUNCTION
4.
INSUFFICIENT HEATING
TEST OR INSPECTION
Step 1. Check to see that MODE SELECTOR SWITCH is properly positioned.
CORRECTIVE ACTION
Set switch to LOW HEAT or HIGH HEAT.
NOTE
During LOW HEAT operation only, one bank (nine) of the heaters is operational.
The TEMPERATURE CONTROL thermostatically controls these heaters.
During HIGH HEAT operation, an additional second bank (six) of heaters
operates continuously.
TEST OR INSPECTION
Step 2. Check that TEMPERATURE CONTROL is set to WARMER position.
CORRECTIVE ACTION
Set TEMPERATURE CONTROL to WARMER position (see WP0006).
TEST OR INSPECTION
Step 3. Inspect fresh and return air filters for dirt or blockage (see WP0027).
CORRECTIVE ACTION
Clean filter/remove blockage.
TEST OR INSPECTION
Step 4. Check relays K4 and K5. (See WP0038).
CORRECTIVE ACTION
Replace if found bad.
TEST OR INSPECTION
Step 5. Check thermostatic switches S2 and S3. (See WP0020).
CORRECTIVE ACTION
Replace if found bad.
0010 00-8