TM9 4120-423-14&P
4.
INSUFFICIENT HEATING - Continued
TEST OR INSPECTION
Step 6. Check temperature-sensing probe A1-RT. (See WP0019).
CORRECTIVE ACTION
Replace if found bad.
TEST OR INSPECTION
Step 7. Check mode selector switch S1. (See WP0059).
CORRECTIVE ACTION
Replace if found bad.
TEST OR INSPECTION
Step 8. Check heaters HR1-HR15. (See WP0021).
CORRECTIVE ACTION
Replace if found bad.
MALFUNCTION
5.
RUN INDICATOR LIGHT DOES NOT ILLUMINATE WITH AIR CONDITIONER
OPERATING
TEST OR INSPECTION
Press light in. Light should illuminate.
CORRECTIVE ACTION
Replace bulb (see WP0060).
MALFUNCTION
6.
TEMPERATURE CONTROL NOT EFFECTIVE
TEST OR INSPECTION
Step 1. Check temperature control A1. (See WP0061).
CORRECTIVE ACTION
Replace if found bad.
TEST OR INSPECTION
Step 2. Check temperature-sensing probe A1-RT. (See WP0019).
CORRECTIVE ACTION
Replace if found bad.
TEST OR INSPECTION
Step 3. Check mode selector switch. (See WP0059).
CORRECTIVE ACTION
Replace if found bad.
0010 00-9
|