TM9 4120-423-14&P
TEMPERATURE SENSING PROBE (A1-RT)
THIS WORK PACKAGE COVERS:
Inspection of Installed Items
Removal
Installation
Tools and Special Tools
Screwdriver
Wrench
Materials/Parts
Temperature Sensing Probe SP4781
Adhesive, Sealant
MIL-A-46106, Type I
Personnel Required
Unit Technician
Equipment Conditions
Air conditioner removed from shelter (See
Return air screen and frame removed (See
Front evaporator cover removed (See
INSPECTION OF INSTALLED ITEMS
1
Disconnect the two quick-disconnect terminals from the P4 to J15 harness.
2
Check resistance between probe leads. Resistance should be zero. If it is not, replace the
temperature-sensing probe.
3
Check that probe leads are securely attached to probe and that probe is in good condition. If it is
bent, dented, or otherwise damaged, replace it.