TM9 4120-423-14&P
ASSEMBLY
1
On a level surface, place the back of the evaporator assembly next to the front of the condenser
section. (Metal hose assemblies and slit in feed through gaskets and mounting holes should
match.)
2
Carefully guide the refrigerant metal hose assemblies through the evaporator housing opening
and slide the evaporator and condenser assemblies together.
3
Use open end wrenches and connect the low and high condenser to evaporator assembly half
4
Leak test the connections (See WP0073).
5
Connect J2 and J9 connectors.
6
Move the two sections snug against each other and align the holes.
7
Using socket or combination wrench, secure the evaporator and condenser assemblies together
with four each hex head cap screws, lockwashers, and flat washers.
8
Install left end condenser cover. (See WP0045).
9
Install right end condenser cover. (See WP0045).
10
Install access cover. (See WP0024).
11
Install air conditioner on shelter. (See WP0006).
END OF TASK
0014 00-3
|