TM9 4120-423-14&P
INSTALLATION
If the old probe is to be reinstalled, skip to step 3.
1
The sensing probe will be supplied with leads. Slip insulation sleeving over each lead for the
entire length, approximately 20 inches (50.8 cm).
2
Install a quick-disconnect terminal on each of the two probe lead ends.
3
If the sensor bracket was removed, use a screwdriver and wrench and install the bracket with the
two screws and locknuts.
4
Reapply adhesive sealant between probe and bracket.
5
Work the leads through the side panel and connect the two quick-disconnect terminals to the
terminals on the P4 to J15 harness.
6
Slip the insulation sleeving over the quick-disconnect terminals.
7
Install the front evaporator cover. See WP0025.
8
Install the return air screen and frame. See WP0027.
9
Install the air conditioner on the shelter. See WP0006.
END OF TASK
0019 00-3
|