TM9 4120-423-14&P
6
Remove the connector (J7) harness and connector gasket from the backside of the cover. Take
care that the connector gasket is not lost.
7
Slide the radio frequency filter out and disconnect the P8 plug and harness from the backside of
the filter.
INSTALLATION
1
Connect the P8 plug and harness to the J8 connector on the backside of the filter.
2
Using a screwdriver, socket and ratchet, attach the remote control harness connector (J7) and
connector gasket to the front evaporator cover with four screws and locknuts.
3
Align the holes in the EMI gasket, radio frequency filter and front evaporator cover.
4
Using a screwdriver, install the two bottom screws in the cover and radio frequency filter.
5
Using a screwdriver, attach the chain ends for the protective connector cap and cover when the
two top radio frequency filter mounting screws are installed.
6
Line up screw holes in cover and air conditioner housing.
7
Using screwdriver, install cover with eight screws.
8
Install air conditioner on shelter. See WP0006.
TESTING
1
Continuity test the filter. Replace if found bad.
2
Continuity-Test J1 to J8, A to A, B to B, C to C, D to D
NOTE
Continuity testing does not necessarily predict the behavior of capacitors under load. If
the filter still does not operate properly after passing the continuity test, substitute a filter
known to be good.
0023 00-3
|