TM9 4120-423-14&P
17
Using screwdriver, secure the module mounting screws.
18
Connect the P2A, P3, P4, and P6 connector plugs.
19
Install top evaporator cover. See WP0026.
TESTING
WARNING
Disconnect input power to the air conditioner before performing any maintenance to the
electrical system. Voltages used can be lethal. Shutting the unit off at the control module
does not disconnect power to the various components of the air conditioner.
Motor (B3) Test Point
P6 MOTOR PLUG
1
Remove connector plug P6 from connector J6.
2
Using multimeter, check all P6 pins for shorts. Pin D is ground. Check pins A, B, C, E, and F to
pin D. There should be no reading. Check pin D to motor frame. Multimeter should read zero.
0030 00-7
|