TM9-4120-423-14&P
3
Using multimeter, check resistance of 3 phase motor windings at P6: A to B, B to C, A to C
Resistances should all be above zero, but below 12 ohms.
4
Using multimeter, check resistance between pins E and F. Resistance should be zero, meaning
thermostatic switch is closed.
5
If motor fails any of the above tests, replace it.
6
If motor passes all of the tests above, check wiring connections between J6 and K3. (See wiring
diagram).