TM9-4120-423-14&P
6
Check general condition of blind nuts and snap fasteners. Repair if loose, replace if damaged or
missing.
REPAIR OR REPLACEMENT
1
To replace danger plate, use a drill bit slightly smaller than the diameter of the rivets.
2
Drill the rivets out and remove the danger plate.
3
Install danger plate with four rivets.
NOTE
Prior to removal of old gasket material, cut the new replacement material to size using the
old item as a sample.
4
Remove as much old gasket or insulation material as possible by pulling or scraping it away
from the metal surface.
WARNING
Dry Cleaning Solvent is flammable, and its vapors can be explosive. Repeated or
prolonged skin contact or inhalation of vapors can be toxic. Use a well-ventilated area,
and keep away from sparks or flame. Use goggles, gloves, and apron when appropriate.
5
Soften and remove old adhesive and gasket residue, using dry cleaning solvent and a stiff brush.
6
Use only approved replacement material as specified in Chapter 8.
7
EMI gasket material and regular gasketing specified for this unit are supplied with adhesive
backing.
8
Cut gasket to size. Be sure that EMI gasket corners are mitered so that good continuous edge
contact is made.
9
Be sure that surface to which gasket is to be applied is clean and free of paint and old adhesive
material.
10
Remove backing material from adhesive side and immediately press gasket in place. Be sure
that good edge-to-edge contact is made on the EMI gaskets.
11
To replace blind nut(s), use a drill bit slightly smaller than blind nut body diameter.
12
Drill out old blind nut(s).
0056 00-2
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |