TM9 4120-423-14&P
3.
INSUFFICIENT COOLING - Continued
(e)
Measure temperatures of air going into (return) and out of (discharge) evaporator
section. Discharge should be 20Ε plus or minus 5Ε F lower than return air
temperature.
TEST OR INSPECTION
Step 9. Check liquid line solenoid valve L2 coil. (See WP0093).
CORRECTIVE ACTION
Replace coil only, if found bad.
TEST OR INSPECTION
Step 10. Check pressure equalizing solenoid valve L1 coil. (See WP0093).
CORRECTIVE ACTION
Replace coil only, if found bad.
TEST OR INSPECTION
Step 11. Check temperature control A1. (See WP0061).
CORRECTIVE ACTION
Replace if found bad.
TEST OR INSPECTION
Step 12. Check temperature-sensing probe A1-RT. (See WP0019).
CORRECTIVE ACTION
Replace if found bad.
TEST OR INSPECTION
Step 13. Check mode selector switch S1. (See WP0059).
CORRECTIVE ACTION
Replace if found bad.
TEST OR INSPECTION
Step 14. Check solenoid L2 valve body action. (See WP0093).
CORRECTIVE ACTION
Replace solenoid valve if found bad.
TEST OR INSPECTION
Step 15. Check solenoid L1 valve body action. (See WP0093).
CORRECTIVE ACTION
Replace solenoid valve if found bad.
TEST OR INSPECTION
Step 16. Check evaporator expansion valve. (See WP0078).
CORRECTIVE ACTION
Replace if found bad.
0067 00-9
|