REFRIGERANT R-22 PRESSURE CHECK
THIS WORK PACKAGE COVERS:
Operational Check
Tools and Special Tools
Pressure Gauges
Servicing Manifold
Personnel Required
Direct Support Technician
Equipment Conditions
Air conditioner removed from shelter, if
necessary
Refrigerant R-22 system discharged (See
Refrigerant R-22 system purged (See
Any brazing/debrazing procedure completed
(See WP0072)
Refrigerant R-22 system recharged (See
OPERATIONAL CHECK
Except in cases where it is obvious that the Refrigerant R-22 charge has been lost, the first step in
troubleshooting problems in the refrigeration system should be to check discharge and suction pressures
under operating conditions. Check pressures as follows:
1
Turn the MODE SELECTOR SWITCH to OFF.
2
Connect individual pressure gages, or a refrigeration servicing manifold and hoses to the high
(discharge) and low (suction) service valves.
3
Open the low (suction) and high (discharge) service valves.
0076 00-1