![]() TM9 4120-423-14&P
5
Apply locking compound to solenoid valve mounting screw threads.
6
Using screwdriver, secure valve body to mounting bracket with two screws, lockwashers, and
flat washers.
7
Reassemble the internal components in the valve body and install the tube and plunger assembly,
and two attaching screws.
8
Remove and discard grommet supplied with coil.
9
Install replacement grommet in coil.
10
Cut solenoid valve coil leads to 6.00 plus or minus 0.25 inches (15.24 plus or minus 0.63 cm)
long.
11
Install quick disconnect terminal lugs on ends of both leads.
12
Slip the coil assembly and data plate onto the body tube and plunger assembly.
13
Using wrench, secure the coil with a nut.
14
Connect leads to disconnect splices.
15
Replace the dehydrator. (See WP0080).
16
Leak test all newly connected joints and all tube connections in the area. (See WP0073).
17
18
Install left end condenser cover. (See WP0045).
19
Install top condenser cover. (See WP0044).
20
Connect power.
END OF TASK