TM9 4120-423-14&P
EVACUATING THE REFRIGERANT R-22 SYSTEM
THIS WORK PACKAGE COVERS:
Servicing
Tools and Special Tools
Charging Manifold
Vacuum Pump
Personnel Required
Direct Support Technician
Equipment Conditions
Air conditioner removed from shelter, if
necessary
Refrigerant R-22 system discharged (See
Refrigerant R-22 system purged (See
Refrigerant R-22 system checked for leaks
(See WP0073)
New filter-drier installed (See WP0080)
SERVICING
The refrigeration system must be evacuated to remove all moisture before it is charged with Refrigerant-
22.
CAUTION
Don't evacuate a leaking system. The vacuum created can cause air, moisture, and dirt to
enter system.