WARNING
When handling coils, wear gloves to avoid cuts and reduce fin damage on the coil.
1
Carefully tilt coil and place into position in housing, through left end.
2
Using screwdriver, secure coil to housing with ten screws.
3
No air passage is permitted at top or bottom of condenser coil. Seal these areas with insulation.
Bond the insulation in place with adhesive.
4
While purging the system with nitrogen, braze the tubing joints. (See WP0071and WP0072).
5
Install the following components:
6
Solenoid valve (L1), bracket, and related piping per WP0093 and WP0094.
7
Compressor per WP0097.
8
Low pressure switch per WP0086.
9
High pressure switch per WP0085.
10
Relief valve and related piping per WP0087.
11
Replace the dehydrator. (See WP0080).
12
Check to be sure all tubing has been reconnected.
13
Leak test all newly connected joints and those in the repair area. (See WP0073).
14
Evacuate and charge the Refrigerant R-22 system. (See WP0074 and WP0075).
15
Install condenser guard and condenser inlet EMI screen. (See WP0046).
16
Install left and right end condenser covers. (See WP0045).
17
Install top condenser cover. (See WP0044).
18
Install air conditioner on shelter. (See WP0006).
END OF TASK