TM9-4120-423-14&P
19
You must clean the entire refrigeration system after a burnout has occurred, since contaminants
will have been carried to many corners and restrictions in the piping and fittings. These
contaminants will soon mix with new Refrigerant R-22 gas and compressor oil to cause repeated
burnouts.
20
Remove the filter-drier, and blow down each leg of the refrigeration system. To do this, connect
a cylinder of dry-nitrogen to each filter-drier connection, in turn, and open the cylinder shutoff
valve for at least 30 seconds at 50 psig (3.5 kg/square centimeter) pressure.
21
Connect the two filter-drier fittings with a jumper, locally manufactured from refrigerant tubing
and fittings.
22
Clean system by back flushing with liquid R-11 from pressurized cylinder or circulating pump
and reservoir with pressure of at least 100 psig.
23
If pump is used, connect the discharge line of the Refrigerant R-22 system to the discharge side
of pump.
24
Connect a line containing a filter to the suction line in the unit.
NOTE
An unused filter-drier or other suitable medium may be used as the filter.
25
The other end of the temporary suction line should be connected to a small drum or suitable
reservoir.
26
A line should be run from the bottom of the reservoir to the inlet of the pump.
WARNING
If compressor burnout is suspected, use care when handling compressor to avoid touching
compressor sludge. Acid in sludge can cause burns. Avoid inhaling fumes and burns
from any acid formed by burnout of oil and Refrigerant R-22. Wear gas mask if area is
not thoroughly ventilated. Wear protective goggles or glasses to protect eyes. Wear
rubber gloves to protect hands. Use care to avoid spilling compressor burnout sludge. If
sludge is spilled, clean area thoroughly.
27
Fill reservoir with fluorocarbon Refrigerant R-11, and start the pump. Continue filling the
reservoir with Refrigerant, R-11, until it begins to pour out of the return line. Continue flushing
for at least 15 minutes.
28
Reverse the pump connections, replace the filter with a new filtering medium, and back flush the
system for an additional 15 minutes.