TM 9-4120-428-14
OPERATOR'S MAINTENANCE
AIR CONDITIONER, HORIZONTAL, COMPACT
(NSN 4120-01-502-1319)
OPERATIONAL CHECKOUT AND TROUBLESHOOTING PROCEDURES
USE OF TROUBLESHOOTING TABLE
Troubleshooting Procedures (Table 1) contains troubleshooting information useful to operators in diagnosing and correcting
malfunctions or unsatisfactory operation of the air conditioner. The table lists the common malfunctions an operator is most
likely to encounter. Corrective actions indicate what steps the operator should take.
The operator should determine the malfunction symptom that most closely describes the immediate situation and then
perform the corrective action steps in the order listed.
This manual does not list all possible malfunction symptoms that may be encountered, nor can it list all possible corrective
actions.
A malfunction or corrective action beyond the scope of the operator's capabilities must be reported to unit maintenance.
Table 1. Troubleshooting Procedures
MALFUNCTION 1
UNIT DOES NOT START
SYMPTOM
Air conditioner does not start in any mode.
MALFUNCTION
No power connection.
CAUTION
During cool weather, DO NOT start in COOL mode for at least four hours.
CORRECTIVE ACTION
Re-connect input power if disconnected.
Check to see if CONTROL CIRCUIT BREAKER or COMPR CIRCUIT BKR has tripped.
CORRECTIVE ACTION
Reset the circuit breakers.
0008 00-1
|