AIR CONDITIONER, HORIZONTAL, COMPACT
OPERATIONAL CHECKOUT AND TROUBLESHOOTING PROCEDURES
MALFUNCTION 1
UNIT DOES NOT START
SYMPTOM
Air Conditioner does not start in any mode
MALFUNCTION
No input power connection.
CORRECTIVE ACTION
If power has been disconnected, re-connect the power.
CAUTION
If the input power has been disconnected for an unknown period of time, DO NOT start the unit in COOL MODE until the
power has been reconnected for at least four hours.
Circuit breakers are tripped.
CORRECTIVE ACTION
Reset the circuit breakers.
Loose or damaged electrical connectors and damaged wires in wiring harness.
CORRECTIVE ACTION
Tighten or replace connectors or repair damaged wires as necessary.
No internal wiring for correct connection.
CORRECTIVE ACTION
Be sure internal wiring is connected to terminal board TB3.
There are defective circuit breakers.
CORRECTIVE ACTION
Replace as necessary. (WP 0033 00).
There is a defective MODE SELECTOR switch.
CORRECTIVE ACTION
Replace if defective. (WP 0032 00).
0010 00-1