TM 9-4120-428-14
0010 00
There is no continuity in the pins.
CORRECTIVE ACTION
Test the compressor motor by checking the continuity of the following pins, at
the compressor electrical receptacle. (WP 0016 00) and (WP 0090 00).
a)
Continuity should exist in pins A and B, B and C, and C and A.
b) Continuity should NOT exist in pins A, B, and C, and the compressor
housing.
c) In pins D and E, continuity should exist when the compressor is cool
enough for the internal thermostat to be closed. If the compressor is hot, let
it cool down and then retest.
MALFUNCTION 6
COMPRESSOR SHORT CYCLES
SYMPTOM
The compressor short cycles.
MALFUNCTION
There are obstructions in front of the condenser screen.
CORRECTIVE ACTION
Remove any obstructions and/or roll up and secure the canvas cover.
There is dirt inside the condenser coil.
CORRECTIVE ACTION
Clean the condenser coil if necessary. (WP 0057 00).
The HIGH PRESSURE cutout switch and RESET is tripped.
CORRECTIVE ACTION
RESET the switch, then push and release the HIGH PRESSURE switch.
The LOW PRESSURE cutout switch is tripped.
CORRECTIVE ACTION
RESET the LOW PRESSURE switch, then push and release the LOW PRESSURE
switch.
MALFUNCTION 7
COMPRESSOR STARTS THEN STOPS DURING OPERATION
SYMPTOM
Compressor Starts, then goes out on overload.
MALFUNCTION
The condenser fan motor experiences a failure.
CORRECTIVE ACTION
Observe the condenser fan motor for failure and replace the motor if necessary.
The condenser coil or guard is dirty.
CORRECTIVE ACTION
Clean the coil and/or the guard.
The air outlet louvers are stuck or jammed in a closed position.
0010 00-5
|