0010 00
MALFUNCTION 5
COMPRESSOR WILL NOT START
SYMPTOM
The compressor will not start.
MALFUNCTION
The compressor, control circuit breaker, and selector switches are not properly set.
CORRECTIVE ACTION
Reset the controls.
The contacts of the HIGH-or-LOW cut out switches are open.
CORRECTIVE ACTION
Reset the pressure switches. Notify your supervisor if condition continues.
There are loose electrical connections or faulty wiring.
CORRECTIVE ACTION
Tighten any loose connections and fix any faulty wiring. (WP 0028 00) and (WP
The control circuit breakers or selector switches are not properly set.
CORRECTIVE ACTION
Conduct continuity checks on the control circuit breakers or selector swi tches to
ensure they are properly set. If necessary, fix any open circuits and replace
wires.
The phase sequence relay is not operating properly.
CORRECTIVE ACTION
If necessary, replace bad relay.
There is no continuity across primary and secondary winding of the control transformer for
defective windings.
CORRECTIVE ACTION
If necessary, replace transformer. (WP 0049 00).
The forward and reverse resistances of the rectifier assembly diodes are not operating properly.
CORRECTIVE ACTION
If necessary, replace the bad rectifier. (WP 0048 00).
The operation of the time delay relay is not timed correctly.
CORRECTIVE ACTION
Observe the operation of the time delay relay. If necessary, replace the bad
The compressor relay is not operating properly.
CORRECTIVE ACTION
Substitute the compressor relay, known to be good, check the operation and
replace the bad relay if necessary.