TM 9-4120-428-14
0012 00
The pressure regulator valve is defective .
CORRECTIVE ACTION
Check the pressure regulator valve and replace if defective. (WP 0081 00).
The primary expansion valve is not operating properly.
CORRECTIVE ACTION
Check the primary expansion valve for proper operation and replace if defective.
The quench valve is not operating properly.
CORRECTIVE ACTION
Check the quench valve for proper operation and replace if defective. (WP 0078
TROUBLESHOOTING PROCEDURE
REFRIGERANT SYSTEM CONTINUOUSLY LOSING REFRIGERANT
SYMPTOM
The air conditioner is continuously losing refrigerant.
MALFUNCTION
The refrigerant tubing and its components show signs of leaking.
CORRECTIVE ACTION
WARNING
Unit contains R-22, a chemical substance that harms public health and the environment
by destroying ozone in the upper atmosphere.
CAUTION
Qualified personnel should service the equipment.
1. Check the refrigerant tubing and its components for leaks using a leak detector; repair or
replace defective parts as necessary. (WP 0091 00).
2. Check the pressure relief valve and replace if defective. (WP 0086 00).
TROUBLESHOOTING PROCEDURE
UNIT OPERATES CONTINUOUSLY ON COOL
SYMPTOM
The unit continuously operates on cool.
MALFUNCTION
Solenoid valve L1 is defective.
CORRECTIVE ACTION
Check solenoid valve L1 and replace if defective . (WP 0079 00).
0012 00-3
|