TM 9-4120-428-14
DIRECT SUPPORT MAINTENANCE
AIR CONDITIONER, HORIZONTAL, COMPACT
(NSN 4120-01-502-1319)
PRESSURE REGULATOR REPLACEMENT
INITIAL SETUP:
Equipment Condition
Tools
Remove actuating cylinder (WP 0082 00)
Refrigeration Unit Service Tool Kit, WP 0000 00, Item
1
Materials/Parts
Pressure Regulator
Lock Washer
1
2
5
4
3
5
6
REPLACEMENT
1. Remove screw (1), lock washer (2), clamp (3), and post spacer (4).
2. De-breeze two tube connections (5) and remove pressure regulator (6). (See WP 0067 00).
3. Slip the pressure regulator (6) in place.
4. Braze the tubing to the pressure regulator (6) (See WP 0067 00).
5. Secure the pressure regulator (6) with screw (1), lock washer (2), clamp (3), and post spacer (4).
NOTE
FOLLOW-ON MAINTENANCE:
Install actuating cylinder (WP 0082 00)
END OF WORK PACKAGE