TM 9-4120-428-14
0048 00
REPLACEMENT
1. Tag and disconnect ALL wire leads.
2. Remove screw (1) and pull the rectifier (2) from the unit.
3. Cut the terminals from the wire leads and capacitors (C1 and C2 for 3 -phase units).
4. Remove the capacitors (3 and 4).
NOTE
When rectifier CR1 is replaced, capacitors (C1 and C2 for 3-phase units) should also be
replaced.
5. See WP 0028 00, Wiring Diagram. Using the tags, attach capacitors (3 and 4) and wire leads to their respective
terminals.
6. See WP 0028 00, Wiring Diagram. Connect the terminals to the rectifier (2) and remove tags.
7. Install the rectifier (2) using the screw (1).
NOTE
FOLLOW-ON MAINTENANCE:
Install Junction Box (WP 0036 00)
Install Top Front Panel (WP 0019 00)
END OF WORK PACKAGE