TM 9-4120-428-14
DIRECT SUPPORT MAINTENANCE
AIR CONDITIONER, HORIZONTAL, COMPACT
(NSN 4120-01-502-1319)
CHARGING THE REFRIGERATION SYSTEM
INITIAL SETUP:
Materials/Parts
Tools
Refrigerant R-22, WP 0000 00, Item 4
Refrigeration Unit Service Tool Kit, WP 0000 00, Item
1
Equipment Condition
Goggles, WP 0000 00, Item 2
Gloves, WP 0000 00, Item 2
Evacuate the refrigerant system (WP 0070 00)
WARNING
Dangerous Chemical Refrigerant Under Pressure is used in the operation of this
equipment.
Use great care to avoid contact with the liquid refrigerant or inhaling refrigerant gas that
is discharged from any container that is pressurized. Sudden and irreversible tissue
damage can result from freezing. Wear thermal protective gloves and a face protector or
safety glasses in any situation when skin or eye contact is possible.
Prevent contact of refrigerant gas with a flame or other hot surfaces. Heat causes the
refrigerant to break down and form carbonyl chloride (phosgene), a highly toxic and
corrosive gas. Unit contains R-22, a chemical substance that harms public health and the
environment by destroying ozone in the upper atmosphere. Qualified personnel must
service equipment only.
Never introduce high discharge pressure into a refrigerant cylinder. This can cause the
cylinder to rupture and injure personnel.
VAC
VACUUM VALVE
VACUUM PUMP
HIGH
PRESSURE
GAUGE VALVE
REF
CHARGE
VALVE
RED 1/4 IN.
PRESSURE GAUGE
HOSE (HIGH)
LOW
HIGH
COMPOUND
PRESSURE
GAUGE VALVE
CHARGING
LOW
VALVE
PRESSURE
YELLOW 3/8 IN.
VACUUM HOSE (VAC)
CHARGING VALVE
YELLOW 1/4 IN.
CHARGE HOSE (REF)
BLUE 1/4 IN.
COMPOUND GAUGE
HOSE (LOW)
0071 00-1
|