Click here to make tpub.com your Home Page

Page Title: CONDENSER COIL REPLACEMENT
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 9-4120-428-14
DIRECT SUPPORT MAINTENANCE
AIR CONDITIONER, HORIZONTAL, COMPACT
CONDENSER COIL REPLACEMENT
INITIAL SETUP:
Equipment Condition
Tools
Remove dehydrator (WP 0075 00)
Refrigeration Unit Service Tool Kit, WP 0000 00, Item
Purge refrigerant system (WP 0066 00)
1
Remove condenser air inlet guard (WP 0020 00)
Gloves, WP 0000 00, Item 2
Remove connector (WP 0043 00)
Materials/Parts
Condenser Coil
Lock Washers (3)
REPLACEMENT
1. Remove two screws (Item 1), lock washers (2), and mounting plate (3).
2. Remove four screws (4) and two clamps (5) from the receiver (6).
3. Remove screw (7), nut (8), lock washer (9), and clamp (10) from coil (11).
4. De-braze the tube connection (12) on the coil (11) (WP 0067 00).
WARNING
When handling coils, wear gloves to avoid cuts and reduce fin damage.
5. Carefully lift the condenser coil (11), sight glass (13), and receiver (6) up and out of the unit.
6. Remove (de-braze) the receiver (6). (WP 0067 00).
7. Braze the receiver (6) to the new coil. (WP 0067 00)
8. Remove (de-braze) the sight glass (13). (WP 0067 00)
9. Braze the sight glass (13) to the new coil. (WP 0067 00).
0087 00-1

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business