Table 1. Operator Preventive Maintenance Checks and Services (PMCS)
NOTE
Within designated intervals, these checks are to be performed in the order listed. Refer to Figure 1.
ITEM
ITEM TO BE
EQUIPMENT NOT
NO.
INTERVAL
CHECKED OR
PROCEDURE
READY/AVAILABLE
SERVICED
IF:
1
Before
Ground Stud
Ensure unit is grounded with stud near
Unit not grounded.
control module.
2
Before
Panels and Covers
Inspect for security of attachment and
Panels or covers
cleanliness. Report damaged condition to
missing or severely
Unit Maintenance personnel.
damaged.
3
Before
Fresh Air Filter
Inspect for cleanliness, obstructions, and
Filter obstructed,
insecure mountings. Remove obstructions.
damaged, loose,
missing or requires
cleaning.
4
Before
Inspect for cleanliness, obstructions,
Guard requires
Guard
damage, and security of attachment. Report
cleaning, if obstructed,
damaged condition to Unit Maintenance
damaged, loose or
personnel.
missing.
5
Before
Inspect for cleanliness, obstructions,
Louver requires
Discharge Louver
damage, and security of attachment. Report
cleaning, if obstructed,
damaged condition to Unit Maintenance
damaged, loose or
personnel.
missing.
6
Before
Inspect for cleanliness, obstructions,
Louver requires
Intake Louver
damage, and security of attachment. Report
cleaning, if obstructed,
damaged condition to Unit Maintenance
damaged, loose or
personnel.
missing.
7
Before
Condenser Louvers
Check for insecure mountings and damaged
Louvers require
louver blades. Report damaged condition to
cleaning if obstructed,
Unit Maintenance personnel.
damaged or loose.
8
Before
Information Plates
Check for security and legibility.
9
Before
Condensate Drain
Inspect drains for obstructions. Remove
Obstructions cannot be
Tubes
obstructions as required.
removed.
10
Before
Control Module
Ensure knobs are in place and check to see
Knobs are missing or
that switches function properly. Report
switches do not
damaged condition to Unit Maintenance
function properly.
personnel.
0010 00-2