Click here to make tpub.com your Home Page

Page Title: DIRECT SUPPORT TROUBLESHOOTING PROCEDURES - continued
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 9-4120-430-14
0042 00
FAULT PROCEDURE 4.
COMPRESSOR STARTS, BUT STOPS AT ONCE OR AFTER SHORT RUN
PERIOD. (Due to Tripped High Pressure Switch)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
COMPRESSOR STARTS, BUT STOPS
Step 1.
Perform pressure testing on system to determine if an overcharge of refrigerant is indicated. See WP
If overcharged, partially discharge the system and retest. See WP 0044 00 and WP 0050 00.
Step 2.
Check for proper operation of condenser fan and motor.
Replace bad motor or fan. (Refer to WP 0037 00.)
Step 3.
Inspect condenser coil, intake grill and condenser discharge louvers for dirt, obstructions or closed
discharge louver.
Clean or remove obstruction or set discharge louver to full open. See WP 0060 00.
Check linear-actuator linkage for missing hardware.
Step 4.
Turn off power; short-circuit (jumper) the high pressure switch. Turn on power, wait one minute for
time delay to allow compressor to start. Allow compressor to run for a maximum of 12 seconds to
see whether compressor operates normally.
If operation of unit is satisfactory, replace faulty high pressure switch. See WP 0055 00.
FAULT PROCEDURE 5.
COMPRESSOR STARTS, BUT STOPS AT ONCE OR AFTER SHORT RUN
PERIOD. (Due to Tripping of Compressor Internal Overload)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
COMPRESSOR STARTS, BUT STOPS
CAUTION
Do not exceed 12-second operating time for compressor as high pressure may develop in
the refrigeration system that could cause the pressure relief valve to open or may result in
damage to the system.
Step 1.
Check compressor current draw at moment of trip.
If over specified current draw, replace faulty compressor. See WP 0059 00.
Step 2.
Check for proper operation of refrigerant expansion valve superheat at compressor suction.
If in excess of 25 degrees F (-3.88 degrees C) replace expansion valve. See WP 0057 00.
0042 00-4

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business