|
|
TM 9-4120-430-14
0042 00
FAULT PROCEDURE 7.
COMPRESSOR RUNS BUT DOES NOT COOL - Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
COMPRESSOR RUNS BUT DOES NOT COOL
Step 6.
Check for high discharge pressure. (Refer to Table 1, WP 0050 00.)
Bleed off excess refrigerant.
Step 7.
Check operation of liquid solenoid valve. Unit may be in standby operation.
Check continuity of solenoid coil. Replace defective coil. Cycle equipment several times.
Perform refrigeration system pressure testing for low or expected discharge pressure. Refer to
FAULT PROCEDURE 8.
COMPRESSOR EXCESSIVELY NOISY
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
COMPRESSOR EXCESSIVELY NOISY
Step 1.
Listen for knocking.
Check for low suction line temperature indicating that liquid refrigerant is returning to
compressor. (Refer to WP 0050 00 and Table 1, WP 0050 00.)
Step 2.
Check for high discharge pressure indicating overcharge of refrigerant. (Refer to WP 0055 00 and
Table 1, WP 0050 00.)
Bleed off excess refrigerant. Check HIGH pressure switch.
Step 3.
Check three phase power sequence, must be A-B-C for proper compressor rotation.
Refer to schematic diagram (WP 0038 00) for proper connections.
FAULT PROCEDURE 9.
SUCTION PRESSURE TOO LOW
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
SUCTION PRESSURE TOO LOW
Step 1.
Stop compressor and check expansion valve.
Remove remote bulb in suction line. Place bulb in ice water for 1-2 minutes. Start compressor.
Remove bulb from ice water and hold it in one hand to warm it. At the same time, check the
suction line for rapid change of temperature, which indicates flood-through of liquid refrigerant.
If liquid floods through valve, it is operating satisfactorily. If not, valve or remote bulb is faulty.
CAUTION
Do not let liquid flood back into compressor or compressor will be seriously damaged.
0042 00-6
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |