TM 9-4120-430-14
0047 00
1.
Refrigerant gas leak detector. If an electronic refrigerant gas leak detector is available, it should be used in
accordance with the procedures contained in TM 9-4940-509-14&P, Leak Detector, Refrigerant Gas.
NOTE
The electronic refrigerant gas leak detector is highly sensitive to the presence of a
minute quantity of gas in the air, due to this factor, it is quite effective in the
detection of a small leak. However, due to the rapid dispersion of refrigerant gas into
the surrounding air, difficulty may be encountered in pinpointing large leaks. The
detector must be used in a well-ventilated but draft-free area.
2.
Soap solutions. In this method, a strong solution of a liquid detergent and water is brushed onto all points of possible
leakage while closely watching for the formation of bubbles.
Testing Procedure
To perform leak testing by use of the electronic detector, it is necessary that the system be pressurized with a proportion
of refrigerant gas. To perform leak testing by use of the soap solution method, the system may be pressurized with dry
nitrogen alone.
1.
To pressurize a system that has some refrigerant charge, for either leak testing method:
a.
Remove the hose connection protective caps from the high and low pressure service valves.
b.
Connect the hoses from a charging manifold to the service valves.
NOTE
If it is possible that the problem may not be a leak and that you may not have to
replace a refrigeration system component, refrigerant-22 may be substituted for the
nitrogen in the following test. If nitrogen is used, you will have to discharge,
evacuate, and recharge the system after this test is completed.
c.
Connect a nitrogen pressure regulator and nitrogen bottle to the center hose connection of the charging
manifold.
d.
Open the unit service valves and the charging manifold valves.
Open the nitrogen tank valve and pressurize the system to 300 psig (21.2 kg/cm2).
e.
f.
Perform leak tests.
g.
If a leak is found, discharge and purge the system and repair leak. See specific instructions for components to be
removed.
h.
If a leak was not found and refrigerant-22 was used to pressurize the system, see charging instructions (see WP
2.
To pressurize a system that has been discharged and purged for leak testing with an electronic detector:
a.
Remove the hose connection protective caps from the high and low pressure service valves.
b.
Connect the hoses from a charging manifold to the service valves.
c.
Connect a cylinder of refrigerant-22 to the center hose connection of the charging manifold.
0047 00-2