Figure 4-71.1. Service Valves and Caps and Chains - Models EKP and FGG
Up
TM-5-4120-359-14 Air Conditioner Split Package 18 000 BTU/HR Cooling 30 000 BTU/HR Heating 208 Volt 3 Phase 400 Hertz Manual
Next
SOLENOID VALVES (L1 AND L2) TEST AND COIL REPLACEMENT - 506780235
TM 5-4120-359-14
4-68. SERVICE VALVES
Preliminary Procedures:
1. Disconnect power.
2. Remove right end condenser cover. (See paragraph 3-26.)
3. Remove condenser section electrical module assembly. (See paragraph 4-90.)
a. Removal (Apples to HIGH SIDE and LOW SIDE service valves.)
Figure 4-72. LOW SIDE and HIGH SIDE Service Valves
(1) Discharge the refrigerant system. (See paragraph 4-5.)
(2) Check that cap is loose from valve.
(3) Using wrench, disconnect the flare nut from the back of the valve.
(4) Using screwdriver, remove two screws that hold valve to condenser housing.
(5) Remove valve.
Change 2 4-145