TM 10-4110-262-13&P
0010 00
Table 1. Preventative Checks and Services - Continued.
Item
Intervals
Item to be
Procedures
Equipment not
No.
checked or
ready/available if:
Serviced
3
Before
IC Shelf
If shelves are installed, confirm that
Any shelf is damaged or not
Assembly
10 shelves are installed and
properly supported. Vertical
shelves are supported at all four
supports are damaged.
corners. Inspect the shelves to
Screws or other attachment
ensure that none are damaged or
hardware is missing.
deformed. Verify the top supports
are supporting shelves and rubber
spacers rest against the IC interior
surfaces. Confirm that bottom
shelves are secured to the floor.
4
Before
Interior Light
Inspect the light switch on the
The light switch, light fixture
Assembly,
container interior. Note any
or pilot light is damaged or
Light Switch,
damage to the switch. Confirm that
any of these are non-
Pilot Light
power is connected to the RU.
operational.
Switch on the interior light. Confirm
that the light is illuminated and the
light enclosure is intact. Confirm
that the pilot light on the container
exterior is lit. Switch off the light.
5
Before
Refrigeration
Inspect the inside (evaporator)
Visible damage to housing.
Unit (RU)
section of the RU. Note any
Evidence of refrigerant oil on
Interior
damage to the housing. Inspect for
exterior surface. Notify direct
Section
refrigerant oil residue.
support maintenance.
Missing attachment hardware,
6
Before
RU Exterior
(1) Inspect the eight mounting bolts
loose or unsecured RU,
holding the RU on the IC. All bolts
During
damaged or missing sling
should be in place and the RU
rings, damaged, frayed or
secured to the container.
loose wires, damaged or
(2) Inspect the sling rings for
loose condenser housing,
breaks, cracks or deformation.
damaged or leaking
refrigerant lines, damaged or
(3) Inspect all wires to ensure they
loose control panel, damaged
are in good condition, properly
breaker box.
restrained and securely attached at
both ends.
(4) Confirm that the RU is plugged
into a 208/230 VAC, 50-60 Hz, 3-
phase electrical source.
(5) Inspect the refrigerator outside
section (condenser section)
enclosure and that it is undamaged
and securely attached.
0010 00-2