TM 10-4110-262-13&P
DIRECT SUPPORT MAINTENANCE
ADVANCED DESIGN REFRIGERATOR, 300 CUBIC FOOT (ADR-300)
REFRIGERATION UNIT
SERVICE
INITIAL SETUP
Tools and special tools
References
Tool Kit, Refrigeration Service
None
(WP 0051 00, Table 2, Item 5)
Equipment Conditions
ADR-300 set up and connected to a
Materials and Parts
Refrigerant, R404A (WP 0068 00, Item 16)
power source (See WP 0005 00 for set-up
procedures).
Personnel Required
HVAC Technician (MOS 52C, AFSC 3E1x1) (2)
NOTE
The following procedures involve servicing the refrigeration system.
Some of these service procedures are regulated by Federal, and in some
cases, by State and Local laws. All regulated refrigeration service
procedures must be performed by an EPA certified technician, using
approved equipment and complying with all Federal, State and Local
laws.
Recovering the Refrigerant
The liquid line sight glass allows the operator to determine the amount of charge under the established
operating conditions. The most satisfactory method of recovering the refrigerant is:
1. Connect a manifold gauge assembly to the compressor.
2. Connect the center hose of the manifold gauge assembly to the recovery machine.
3. Recover the refrigerant.
Evacuating the Refrigeration System
1. Connect the manifold gauge assembly.
2. Start the vacuum pump and evacuate the system to 500 microns.