TM 10-4110-262-13&P
DIRECT SUPPORT MAINTENANCE
ADVANCED DESIGN REFRIGERATOR, 300 CUBIC FOOT (ADR-300)
CONDENSER FAN
REMOVE/INSTALL
INITIAL SETUP
References
Tools and special tools
None
Tool Kit, Refrigeration Service
Equipment Conditions
ADR-300 or RU disconnected from all power
Materials and Parts
supplies.
None
Personnel Required
HVAC Technician (MOS 52C, AFSC 3E1x1) (1)
REMOVE
1. Remove the condenser section exhaust grille.
2. Disconnect the electrical power supply to the fan at the connector. Cut the wire ties as necessary.
3. Remove the four bolts that hold the condenser fan in the condenser enclosure. Retain the bolts.
4. Remove the fan from the condenser section.
INSTALL
1. Position the condenser fan in the fan shroud and align the mounting holes.
2. Reinstall the fan mounting bolts. Don't over tighten.
3. Connect the fan wires. Install the new wire ties.
4. Reconnect power to the RU and start the unit. Confirm that the direction of air flow through the
evaporator is from outside, through the coil and then through the fan.
5. If this flow is reversed, stop the unit, disconnect power from the ADR-300 and reverse polarity on the
fan power supply wires.
0032 00-1
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |